Do you have question? Contact us! (36) 1-461-01-70

Industrial (Ex) heating cables

Our self regulating and power limiting trace heating systems for frost protection and temperature maintenance (up to 235°C / depending on cable type) in hazardous areas.

All types of BTV, QTVR, XTV, KTV and VPL familys of self-regulating, parallel circuit heating cables by Raychem.

All types of KT, HKT familys of self-regulating heating cables by Klöpper-Therm.

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 65°C / Maximum maintain or continuous exposure temperature (power on) +65°C and maximum intermittent exposure temperature (power off) +85°C (maximum cumulative exposure 1000 hours):

Raychem

3BTV2-CT            9 W/m @ +10°C
5BTV2-CT            16 W/m @ +10°C
8BTV2-CT            25 W/m @ +10°C
10BTV2-CT          30 W/m @ +10°C

Temperature classification: T6
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 65°C
maximum intermittent exposure temperature (power off): 85°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 20°C, 35 mm @ -60°C

Klöpper-Therm

KT23J                    9 W/m @ +10°C
KT25J                    15 W/m @ +10°C
KT28J                    25 W/m @ +10°C
KT210J                  32 W/m @ +10°C

Temperature classification: T5-T6
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 65°C
maximum intermittent exposure temperature (power off): 85°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -40°C
Minimum bend radius: 12 mm @ -40°C

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 65°C / Maximum maintain or continuous exposure temperature (power on/off) +110°C:

Raychem

10QTVR2-CT      38 W/m @ +10°C
15QTVR2-CT      51 W/m @ +10°C
20QTVR2-CT      63 W/m @ +10°C

 Temperature classification: T4
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on/off): 110°C
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 20°C-nál, 35 mm @ -60°C)

 Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 120°C / Maximum maintain or continuous exposure temperature (power on) +120°C and maximum intermittent exposure temperature (power off) +190°C (maximum cumulative exposure 1000 hours):

Klöpper-Therm

HKT25J                 15 W/m @ +10°C
HKT210J               31 W/m @ +10°C
HKT215J               46 W/m @ +10°C
HKT220J               63 W/m @ +10°C

Temperature classification: T3
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 120°C
maximum intermittent exposure temperature (power off): 190°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -40°C
Minimum bend radius: 25 mm @ -40°C

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 121°C / Maximum maintain or continuous exposure temperature (power on) +121°C and maximum intermittent exposure temperature (power off) +250°C (maximum cumulative exposure 1000 hours):

Raychem

4XTV2-CT        12 W/m @ +10°C
8XTV2-CT        25 W/m @ +10°C
12XTV2-CT      38 W/m @ +10°C
15XTV2-CT      47 W/m @ +10°C
20XTV2-CT      63 W/m @ +10°C 

Temperature classification: T3 (4/8/12/15XTV2-CT), T2 (20XTV2-CT)
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 121°C
maximum intermittent exposure temperature (power off): 250°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 20°C, 51 mm @ -60°C 

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 150°C / Maximum maintain or continuous exposure temperature (power on) +121°C and maximum intermittent exposure temperature (power off) +250°C (maximum cumulative exposure 1000 hours):

Raychem

5KTV2-CT        16 W/m @ +10°C
8KTV2-CT        25 W/m @ +10°C
15KTV2-CT      47 W/m @ +10°C
20KTV2-CT      65 W/m @ +10°C 

Temperature classification: T2
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 150°C
maximum intermittent exposure temperature (power off): 250°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 26 mm @ 20°C, 51 mm @ -60°C

Our power limiting product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 150-230°C (*) / Maximum maintain or continuous exposure temperature (power on) +150-230°C (*) and maximum intermittent exposure temperature (power off) +260°C (maximum cumulative exposure 1000 hours):

* depending on cable type

Raychem – 5VPL2-CT (* 230°C), 10VPL2-CT (* 210°C), 15VPL2-CT (* 180°C), 20VPL2-CT (* 150°C)

5VPL2-CT        15 W/m @ +10°C
10VPL2-CT      30 W/m @ +10°C
15VPL2-CT      45 W/m @ +10°C
20VPL2-CT      61 W/m @ +10°C

Temperature classification: T2-T4 (Use TraceCalc design software or contact for assistance)
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 230°C (5VPL2), 210°C (10VPL2), 180°C (15VPL2), 150°C (20VPL2) 
maximum intermittent exposure temperature (power off): 260°C
Minimum installation temperature: -60°C
Minimum bend radius: 20 mm @ 20°C, 20 mm @ -60°C