Do you have question? Contact us! (36) 1-461-01-70

Industrial (Ex) heating cables

Our self regulating and power limiting trace heating systems for frost protection and temperature maintenance (up to 235°C / depending on cable type) in hazardous areas.

All types of BTV, QTVR, XTV, KTV and VPL familys of self-regulating, parallel circuit heating cables by Raychem.

All types of KT, HKT familys of self-regulating heating cables by Klöpper-Therm.

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 65°C / Maximum maintain or continuous exposure temperature (power on) +65°C and maximum intermittent exposure temperature (power off) +85°C (maximum cumulative exposure 1000 hours):

Raychem

3BTV2-CT            9 W/m @ +10°C
5BTV2-CT            16 W/m @ +10°C
8BTV2-CT            25 W/m @ +10°C
10BTV2-CT          30 W/m @ +10°C

Temperature classification: T6
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 65°C
maximum intermittent exposure temperature (power off): 85°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 20°C, 35 mm @ -60°C

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 65°C / Maximum maintain or continuous exposure temperature (power on/off) +110°C:

Raychem

10QTVR2-CT      38 W/m @ +10°C
15QTVR2-CT      51 W/m @ +10°C
20QTVR2-CT      63 W/m @ +10°C

 Temperature classification: T4
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on/off): 110°C
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 20°C-nál, 35 mm @ -60°C)

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 150°C / Maximum maintain or continuous exposure temperature (power on) and maximum intermittent exposure temperature (power off) +250°C (maximum cumulative exposure 2000 hours):

Raychem

3XTVR2-CT 9 W/m +10°C
5XTVR2-CT 16 W/m +10°C
8XTVR2-CT 25 W/m +10°C
10XTVR2-CT 32 W/m +10°C
12XTVR2-CT 38 W/m +10°C
15XTVR2-CT 48 W/m +10°C
20XTVR2-CT 64 W/m +10°C

Supply voltage: 190 - 277 VAC
Maximum continuous exposure temperature (power on): 150°C
maximum intermittent exposure temperature (power off): 250°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 10°C, 51 mm @ -60°C 

Our self-regulating product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 205°C / Maximum maintain or continuous exposure temperature (power on) +205°C and maximum intermittent exposure temperature (power on/off) +260°C (maximum cumulative exposure 2000 hours):

Raychem

3HTV2-CT 9 W/m +10°C
5HTV2-CT 16 W/m +10°C
8HTV2-CT 25 W/m +10°C
10HTV2-CT 32 W/m +10°C
12HTV2-CT 38 W/m +10°C
15HTV2-CT 48 W/m +10°C
20HTV2-CT 64 W/m +10°C
28HTV2-CT 88 W/m +10°C

Supply voltage: 190 - 277 VAC
Maximum continuous exposure temperature (power on): 205°C
maximum intermittent exposure temperature (power on/off): 260°C (maximum cumulative exposure 1000 hours)
Minimum installation temperature: -60°C
Minimum bend radius: 13 mm @ 10°C, 25 mm @ -60°C

Our power limiting product range for industrial (can be used in hazardous areas) frost protection and temperature maintenance up to 150-230°C (*) / Maximum maintain or continuous exposure temperature (power on) +150-230°C (*) and maximum intermittent exposure temperature (power off) +260°C (maximum cumulative exposure 1000 hours):

* depending on cable type

Raychem – 5VPL2-CT (* 230°C), 10VPL2-CT (* 210°C), 15VPL2-CT (* 180°C), 20VPL2-CT (* 150°C)

5VPL2-CT        15 W/m @ +10°C
10VPL2-CT      30 W/m @ +10°C
15VPL2-CT      45 W/m @ +10°C
20VPL2-CT      61 W/m @ +10°C

Temperature classification: T2-T4 (Use TraceCalc design software or contact for assistance)
Supply voltage: 220 - 277 VAC
Maximum continuous exposure temperature (power on): 230°C (5VPL2), 210°C (10VPL2), 180°C (15VPL2), 150°C (20VPL2) 
maximum intermittent exposure temperature (power off): 260°C
Minimum installation temperature: -60°C
Minimum bend radius: 20 mm @ 20°C, 20 mm @ -60°C

Have you got a question or an idea?

If you have a question regarding heating-cables, cable accessories or HAUPA products, please apply to our colleagues. We are at your disposal with our long-term experience and specialized knowledge.

polynorm-futokabelek-a2 polynorm-futokabelek-b2 polynorm-futokabelek-c2 polynorm-futokabelek-d2 polynorm-futokabelek-e2

We answer!

POLY-NORM 2000 Ltd. H-1147 Budapest Lőcsei út 81. M-Th 8-16 F 8-14 (36) 1-461-01-70 (36) 1-461-01-71 polynorm2000@polynorm2000.hu